A heat-pump retrofit proposal usually shows a payback of three to five years. The same project, audited, often shows eight to twelve. The difference is not the heat pump. It is the arithmetic: the total project cost is used instead of the incremental cost, and a theoretical efficiency rate is used instead of a measured saving.

This article builds a payback that survives an audit. The example is a gas-boiler replacement with 150,000 kWh of annual heat demand. All numbers are illustrative and must be replaced with project data.

Step one: incremental investment

Incremental investment is the new scheme’s total cost minus what the old scheme would cost to keep running. If the old boiler is 12 years old and needs a CNY 120,000 overhaul and burner replacement, that CNY 120,000 is the baseline. It is money the site must spend whether or not it retrofits.

Item Heat pump Old boiler continued Difference
Main plant CNY 240,000 Overhaul and burner CNY 120,000 +120,000
Tank and piping CNY 120,000 Patch repair CNY 10,000 +110,000
Electrical and installation CNY 90,000 CNY 20,000 +70,000
Civil works — CNY 10,000 -10,000
Total CNY 450,000 CNY 160,000 +290,000

The incremental investment is CNY 290,000, not CNY 450,000. Using the total cost overstates the payback by more than 50%. If the old plant has five years of life left, the baseline should be the present value of those five years, not a full replacement; the principle is the same, but the number is smaller.

Step two: net annual saving

Net saving is old running cost minus new running cost minus the change in maintenance. It is not the old bill multiplied by a savings percentage.

Old boiler. Annual heat 150,000 kWh; efficiency 0.85; gas calorific value 9.94 kWh/m³. Gas use = 150,000 ÷ 0.85 ÷ 9.94 = 17,750 m³. At CNY 3.2/m³, the annual gas bill is CNY 56,800.

New heat pump. Annual average COP 3.2. Electricity = 150,000 ÷ 3.2 = 46,875 kWh. At CNY 0.70/kWh, the annual bill is CNY 32,800.

Maintenance. The boiler needs an annual inspection and burner service, about CNY 8,000. The heat pump needs coil cleaning and water treatment, about CNY 6,000. The difference is a CNY 2,000 saving.

Net annual saving = 56,800 − 32,800 + 2,000 = CNY 26,000.

Item Value Basis
Annual heat 150,000 kWh Metered or calculated
Old gas cost CNY 56,800 17,750 m³ at 3.2
New electricity cost CNY 32,800 46,875 kWh at 0.70
Maintenance difference −CNY 2,000 New is lower
Net saving CNY 26,000 Difference

Step three: static and dynamic payback

Static payback = 290,000 ÷ 26,000 = 11.2 years. Dynamic payback, at a 6% discount rate, is about 15.8 years. The static number is the one usually quoted; the dynamic number is closer to the cost of money.

Compare the payback with the equipment life. A heat pump typically lasts 10–15 years. An 11-year static payback means the unit is close to replacement when it pays back. That does not make the project wrong, but it changes the argument: the case may rest on carbon, reliability or a grant, not on pure cash.

Sensitivity: what actually moves the answer

Change Net saving Static payback
Base case CNY 26,000 11.2 years
Gas +CNY 0.30/m³ CNY 31,300 9.3 years
Electricity +CNY 0.10/kWh CNY 21,300 13.6 years
Boiler efficiency falls to 0.75 CNY 33,500 8.7 years
Operating days fall from 300 to 200 CNY 17,300 16.8 years

The gas-to-electricity price spread is the dominant variable. A project that looks attractive at a 3:1 spread can fail at 2:1. The audit should use the site’s actual tariff, including demand charges and time-of-use periods, not a national average.

The evidence an auditor will ask for

Twelve to twenty-four months of bills. Gas and electricity, with the meter numbers and the tariff schedule. A bill from a mild winter is not a baseline.

Weather normalization. Heating demand is not the same every year. Use heating degree days or a regression against ambient temperature. If the site has no sub-meter, estimate the heat load from the boiler run hours and gas use, and state the method.

Boundary. State what is included: main plant, pumps, tank, piping, electrical, civil. A saving that excludes the circulating pump is not a system saving.

Measurement and verification. For a large project, agree a measurement plan before construction: temporary meters, run hours, leaving-water temperature and outdoor temperature. After commissioning, compare a full heating season with the normalized baseline. A one-week test is not an M&V plan.

Four errors to remove

Using total cost instead of incremental cost. The old plant’s unavoidable renewal is not part of the retrofit.

Using nominal COP. The annual average COP includes defrost, part-load and standby. A nominal 4.5 can be an annual 3.0 in a cold climate.

Ignoring maintenance and water treatment. A heat pump with a fouled condenser can lose 10–20% of its capacity. The maintenance line is not zero.

Ignoring the terminal life. A 15-year payback on a 12-year asset is not a payback; it is a donation.

Boundary

A retrofit that keeps the existing tank, piping and electrical room can have a much lower incremental cost than a full replacement. A retrofit that needs a new electrical service, a larger tank or a structural roof change may never pay back. The audit should separate the heat-pump package from the enabling works and show both.

Common questions

What is incremental investment?

The new scheme’s total cost minus what the old scheme would cost to keep running. If the old boiler needs a CNY 120,000 overhaul, that amount is the baseline and is subtracted from the new project cost.

Why is my payback twice the proposal?

The proposal probably used total cost instead of incremental cost, nominal COP instead of annual average, or omitted maintenance and enabling works. Rebuild the number from bills and a normalized baseline.

Static or dynamic payback?

Report both. Static ignores the cost of money; dynamic discounts the cash flow. A 6% discount rate can turn an 11-year static payback into 15–16 years dynamic.

Which variable is most sensitive?

The gas-to-electricity price spread, followed by annual run hours and old-boiler efficiency. A project that works at a 3:1 spread may fail at 2:1.

Can I use one winter’s bills as the baseline?

No. Use 12–24 months and normalize for weather with heating degree days or a regression. A mild winter understates the baseline and flatters the saving.

Is a heat-pump retrofit always worth it?

No. If the incremental cost is high, the price spread is small, or the existing plant has many years of life, the payback can exceed the equipment life. Carbon or reliability may still justify it, but the cash case should be honest.

What counts as incremental investment?

The complete heat-pump solution minus the complete alternative, including tanks, controls, electrical work and commissioning. Do not use the heat-pump invoice alone, and do not include costs that the alternative would also need.

How do I normalize the baseline?

Use at least 12 months of bills, adjust for weather and production, and separate fixed from variable charges. A baseline built from one month or from a design load is not auditable.