A centrifugal chiller is a flow machine. The impeller adds head to the refrigerant gas; the condenser sets the pressure the impeller must overcome. The operating point is where the compressor curve meets the system curve. When the flow falls too far, the point crosses the surge line and the machine reverses flow.
This article explains the head-flow relationship, the stage count, the minimum load and the mechanical room dimensions that are easy to miss. It does not repeat the surge diagnosis; it explains why the machine has a minimum load at all.
Head and flow
A single impeller can produce a pressure ratio of about 2.5–3.0. A 7 °C evaporator and a 37 °C condenser need a pressure ratio above 3.3, so a single stage is not enough. Two stages in series, with an economizer between them, reach 3.0–4.0; three stages reach 4.0–5.0 for high condensing or heat-recovery duty.
| Stage | Pressure ratio | Condensing | Typical size |
|---|---|---|---|
| Single | 2.5–3.0 | ≤40 °C | 300–800 RT |
| Two | 3.0–4.0 | 40–45 °C | 500–1,500 RT |
| Three | 4.0–5.0 | >45 °C | 1,200–3,000 RT |
The economizer takes liquid from the condenser, flashes it to an intermediate pressure and feeds the vapor to the second-stage inlet. The second stage compresses less gas, so the unit power per kW of cooling falls. A two-stage machine with an economizer can be 4–6% more efficient than a single-stage at the same condition.
The minimum load
At low flow, the impeller produces more head than the condenser needs. The gas at the impeller exit cannot leave, so it flows back from the condenser. The flow recovers, the pressure falls, and the cycle repeats. That is surge. It is a property of the machine, not a fault.
The minimum stable load is usually 25–35% without a variable speed drive. A VFD can extend it to about 20% by reducing the speed and the head. A hot-gas bypass can keep the machine online below that, but it wastes cooling capacity and should be a last resort.
| Load | Control | Risk |
|---|---|---|
| 100–70% | Guide vanes open | None |
| 70–50% | Vanes modulating | Low |
| 50–35% | Vanes + VFD | Medium |
| 35–25% | VFD + bypass | High |
| <25% | Stop or small machine | Surge |
A building that falls to 15% load at night should not use one centrifugal machine. A small screw or scroll machine for the base load is a better design than a bypass that wastes 30% of the capacity.
Start current
A large centrifugal compressor can draw 5–6 times its rated current on a direct-on-line start. That is a transformer and switchgear issue, not just a motor issue. A star-delta start reduces it to 2.5–3 times, a soft starter to 2–2.5 times and a VFD to 1.5 times or less. The VFD also gives a smooth acceleration and a lower mechanical shock.
The electrical design should state the starting method and the allowable voltage dip. A 5% dip on a weak supply can trip other equipment. A soft starter is often the cheapest compromise; a VFD is the best if the load profile justifies it.
mechanical room dimensions
Two dimensions are easy to miss. The first is the lifting height: the impeller and the compressor casing need to be removed upward, so leave at least 1.2 m between the top of the machine and the beam. The second is the tube-pull space: the condenser and evaporator tubes need a clear length at the end of the vessel, often 4–6 m. A mechanical room that is too shallow forces the maintenance team to pull the bundle and turn it, which doubles the downtime.
The water pressure drop also belongs in the pump head. An 800 RT centrifugal may have 60–80 kPa evaporator and condenser pressure drop. A pump selected on flow alone will be short at the coil.
When a centrifugal is right
Choose a centrifugal above 800 RT with a load that stays above 50% for most hours. Choose a two-stage machine for a high condensing temperature or an economizer benefit. Choose a screw for a load that swings below 40%, or for a plant that needs a simple base-load machine.
The centrifugal is the most efficient at full load and the least tolerant at low load. The design should use the load duration curve, not the peak load alone.
Refrigerant and oil
A centrifugal chiller often uses a low-pressure refrigerant and a flooded evaporator. The oil is carried by the refrigerant and returned through a purge or an oil return line. A low oil level is not always a leak; it may be a return problem. The purge unit removes air and moisture that enter through a low-pressure seal; a purge that runs continuously indicates a leak.
Check the purge count and the oil level weekly. A rising purge count is an early warning of a leak, before the capacity falls. A falling oil level with a normal purge may be a blocked return line or a failed ejector. Do not add oil without finding where it went.
Boundary
This article covers the compressor and the mechanical room geometry. It does not cover refrigerant selection, oil management or control tuning. A centrifugal that is correctly selected but operated below its minimum load will still surge; the design must include a base-load machine or a load-following control.
Common questions
Why does a centrifugal chiller surge?
At low flow, the impeller produces more head than the condenser needs, so gas flows back. Surge is a property of the machine at the left side of its curve, not a fault.
What is the minimum load?
About 25–35% without a VFD, and about 20% with a VFD. Below that, a hot-gas bypass can keep it online but wastes capacity; a small base-load machine is better.
How many stages do I need?
A single stage covers up to about 40 °C condensing, two stages 40–45 °C, three stages above 45 °C. The choice depends on the pressure ratio, not the capacity alone.
Why does start current matter?
A direct-on-line start can draw 5–6 times rated current. A soft starter reduces it to 2–2.5 times, a VFD to 1.5 times or less. The supply and switchgear must be sized for it.
How much space for tube pulling?
Leave 4–6 m at the end of the vessel for the tube bundle, and at least 1.2 m above the machine for lifting the impeller and casing.
Should I use a centrifugal for a hotel?
Only if the load stays above 50% for most hours. A hotel with a low night load may need a small screw or scroll base-load machine to avoid surge.
Why does minimum load matter?
Below the minimum, the impeller flow approaches the surge line. The chiller may surge, cycle or lose temperature control. The minimum load is a mechanical limit, not a control preference.
How do I read a head-flow curve?
Read the head at the duty flow, then compare with the system curve. The intersection is the operating point. If it is left of the surge line, you need more flow or less head, not a new compressor.
Further technical reading
For surge diagnosis, see Centrifugal Chiller Surge: Diagnose the Operating Point. For the comparison, see Screw versus Centrifugal Chillers. For magnetic bearings, see Magnetic-Bearing Centrifugal Chillers. For installation hold points, see Chiller Installation: 90 Days, Four Hold Points.