Screw Compressor: Rotor, Oil and Vi

A screw chiller is the default for 100–2,000 kW because it balances three things: continuous capacity control, a compact package and tolerance of part-load and wet compression. The balance is not accidental; it comes from the rotor, the oil circuit and the built-in volume ratio.

This article covers those three, not the refrigeration cycle. It explains why a screw machine can run at 10% load without surge, why the oil is the lifeblood and why Vi matters more than the catalog COP.

Rotor and Vi

A twin-screw compressor has two meshing rotors. The gas is trapped in a cavity, the cavity closes and the volume decreases as the rotors turn. The built-in volume ratio, Vi, is the ratio of the cavity volume at suction to the volume at the discharge port. Common values are 2.6, 3.0 and 3.5.

Vi must match the system pressure ratio. If Vi is too high, the gas is over-compressed before the port opens; the compressor uses extra work. If Vi is too low, the gas is under-compressed and back-flows when the port opens; the compressor also uses extra work. A Vi 3.0 machine at a 40 °C condensing temperature may be near its best; at 30 °C, the best Vi is closer to 2.6, and the efficiency loss is about 4%.

Vi Typical condensing Effect
2.6 Low, 30–35 °C Better at cool condenser
3.0 Medium, 35–40 °C General cooling
3.5 High, 40–45 °C High ambient or process

Some screw machines use a slide valve that changes both capacity and Vi. That is why a good part-load screw can hold efficiency at 50% load; the valve is not just a capacity throttle, it is a compression-ratio correction.

Oil is the lifeblood

The oil separates the rotors, seals the gaps, cools the compression and carries debris to the filter. The circuit is: discharge gas carries oil → oil separator → oil cooler → oil filter → injection into the compressor. Each step has a number.

Part Target Failure
Oil separator ≥99.5% separation Oil migrates to condenser, low level
Oil cooler 40–55 °C supply High temperature, low viscosity
Oil filter ΔP <0.1 MPa Bearing starvation
Sight glass 1/3–2/3 level Low-level trip

Oil temperature is the single most useful daily reading. Below 40 °C, the oil is viscous and returns slowly. Above 55 °C, the film thins and the rotors run closer to contact. Above 70 °C, mineral oil oxidizes quickly; synthetic oil can go higher, but the manufacturer’s limit still applies.

Oil return is a long-term issue. Some oil always leaves the compressor. The evaporator must have a return port and a periodic purge, or a flooded evaporator will collect oil at the bottom. A machine that loses oil level over a year is not “using oil”; it is failing to return it.

Part-load behavior

A screw machine can run down to about 10% load with a slide valve, although efficiency falls below 30%. A typical 500 kW machine may have COP 5.2 at full load, 5.6 at 50% and 4.8 at 25%. The peak is often around 75%, not at full load.

That shape is useful for a plant that runs at 50–80% for most hours. It is less useful for a plant that runs at 20% all night; a small screw or a scroll machine may be better for the base load. The staging design should use the part-load curve, not the full-load COP.

A screw machine tolerates a small amount of liquid refrigerant, unlike a centrifugal. That tolerance is not a license for flooding; long-term wet compression dilutes the oil and wears the bearings. Keep the suction superheat within the manufacturer’s range.

When a screw is the right choice

Choose a screw for 100–2,000 kW, a load that varies between 30% and 100%, a mechanical room with limited height and a team that can change oil and filters. Choose a centrifugal above 800 RT with a steady high load; choose a scroll below 150 kW with a simple on/off load.

The screw is not the most efficient at full load and not the cheapest at small size. It is the most tolerant of the middle. That is why it dominates the middle of the market.

Start, unload and stop

A screw compressor should start unloaded. The slide valve closes to the minimum capacity, the motor accelerates, and the valve opens after the oil pressure is established. A start at full load draws a high current and loads the coupling before the oil film is ready. The starter and the control sequence must enforce an unloaded start, even after a power failure.

The stop sequence is the reverse: unload first, then stop the motor, then keep the oil pump running for a few minutes. A sudden stop with a loaded rotor can leave high-pressure gas in the cavity and oil in the wrong place. The next start may be noisy or trip on high pressure.

Oil analysis

An annual oil sample is cheap insurance. Test for water, acidity, viscosity, wear metals and refrigerant dilution. Water above 200 ppm suggests a leak in the oil cooler or a humid site. High iron or copper suggests bearing or rotor wear. Refrigerant dilution lowers the viscosity and can cause a low oil pressure trip.

Do not change oil on a calendar alone. A clean machine in a dry site may go 5,000 hours; a wet site may need 2,000. The sample tells you which. Keep the sample point and the bottle clean; a dirty sample is worse than no sample.

Boundary

This article covers the compressor and the oil circuit, not the condenser or the vessel selection. A screw machine with a fouled condenser or a wrongly sized Vi will not meet its part-load curve. The compressor is one part of the package.

Common questions

What is Vi in a screw compressor?

The built-in volume ratio, the cavity volume at suction divided by the volume at discharge. Common values are 2.6, 3.0 and 3.5. It must match the system pressure ratio.

Why is oil temperature important?

Oil separates, seals and cools the rotors. 40–55 °C is the usual supply range. Below 40 °C, return is poor; above 55 °C, the film thins; above 70 °C, mineral oil oxidizes quickly.

Can a screw chiller run at 10% load?

It can, but efficiency falls below 30%. A slide valve gives continuous control, but a small machine may be better for a long low-load period.

What oil filter pressure drop is too high?

A pressure drop above 0.1 MPa across the oil filter points to a blocked element. Change it before the bearing is starved; a rising oil temperature confirms the restriction.

Does a screw tolerate liquid refrigerant?

Better than a centrifugal, but long-term wet compression dilutes the oil and wears the bearings. Keep superheat within the manufacturer’s range.

Where does a screw fit compared with centrifugal?

Screw is strong at 100–2,000 kW and 30–100% load. Centrifugal is stronger above 800 RT with a steady high load. Scroll is simpler below 150 kW.

How does oil temperature affect efficiency?

Hot oil thins and loses load capacity; cold oil is viscous and raises drag. The oil cooler and the injection temperature set the balance. A rising oil temperature at fixed load often means a fouled cooler or low oil charge.

What happens if the rotor touches?

Contact between rotors or between rotor and casing causes rapid wear, metal debris and loss of compression. It is usually preceded by bearing wear or liquid slugging. Stop the machine and inspect before running again.

Further technical reading

For capacity control, see Screw Compressor Control: Slide Valve or VFD. For the comparison, see Screw versus Centrifugal Chillers. For the three types, see Piston, Scroll or Screw Chillers. For components, see Chiller’s Four Core Components.