1. A heat pump moves heat; it does not make it
On site, a pool heat pump is most often misread as “a more efficient electric heater”. That misreading carries straight into sizing, electrical capacity and the operating-cost budget. An electric resistance heater has a hard physical ceiling: 1 kWh in gives at most 1 kWh of heat, and the ratio is fixed at 1. A heat pump takes a different route. Electricity drives a compressor, and the compressor lifts low-grade heat from outdoor air, ground water or soil into the pool water. The electricity pays for transport, not for the heat itself. At favorable conditions, 1 kWh of electricity delivers 4–6 kWh of heat, and that ratio is the COP.
Three things follow. First, the saving comes from the temperature lift, not from a control board: the warmer the air and the cooler the water, the more lift is available and the higher the COP. Second, output tracks the weather, and a capacity drop during a cold snap is physics, not a fault. Third, anything that damages heat transfer in the pool circuit — scaling, low flow, the wrong exchanger material — goes straight into the energy bill, so maintenance is not optional.
The right question for an owner is not “what is the COP of this unit” but “at my site’s weather, my pool’s set temperature and my circuit’s real flow, how much heat do I get across a year, and how much electricity does it take”.
2. Four actions in a closed loop, four failure modes
The thermodynamic cycle is four actions in series. Lose one and the loop stops delivering.
Evaporation. Liquid refrigerant passes the expansion device, drops in pressure and temperature, and enters the evaporator — on pool units, normally a finned coil. Fans draw outdoor air across the fins; the refrigerant absorbs sensible and latent heat and vaporises. Leaving air is 5–10 K colder than entering air, which is both the visible evidence that heat is being taken out and a quick field check on the air side.
Compression. Low-pressure vapor is compressed to high pressure and high temperature. This step consumes most of the electrical input and produces most of the noise and vibration. A larger pressure ratio means a higher discharge temperature and a harder duty for the compressor and its oil — which is exactly why cold-climate work needs a dedicated low-temperature model.
Condensation. The hot gas enters the condenser and releases heat to the pool water. Pool units use a titanium exchanger here — tube-in-shell or titanium plate — rather than copper or a standard brazed plate, because pool water carries free chlorine, salt and a pH that swings between 7.2 and 7.8.
Expansion. Liquid refrigerant passes an electronic expansion valve or capillary, drops in pressure and temperature, and is ready to absorb heat again.
| Component | Thermodynamic role | What engineering cares about | Typical symptom when it degrades |
|---|---|---|---|
| Evaporator (finned coil) | Takes heat from air; refrigerant vaporises | Fin spacing, airflow, coating, clearance | Capacity fall, frequent frosting, smaller air temperature drop |
| Compressor | Raises pressure and temperature | Pressure ratio, discharge temperature, starting current, vibration | High-pressure or over-current trip, more noise, short cycling |
| Condenser (titanium exchanger) | Rejects heat to pool water | Wall thickness, water velocity, pressure drop, scaling | Weak water temperature rise, high-pressure alarm, rising pressure drop |
| Expansion device | Drops pressure and temperature | Superheat control, modulation accuracy | Liquid return, abnormal suction temperature, capacity hunting |
| Fan | Maintains air-side heat transfer | Airflow, static pressure, speed control | Low airflow, local fin frosting |
| Controller | Closed-loop control and protection | Sensor accuracy, logic, communications | Water temperature swing, nuisance alarms, no link to BMS |
3. Why pool duty is kind to a heat pump
Pool units usually beat domestic-hot-water units on efficiency, and the reason is the duty, not the machine.
Domestic hot water runs to 55–60 °C, so condensing temperature and pressure ratio are high and the compressor works hard. Pool water sits at 26–28 °C for competition and training pools under CJJ 122-2017 and the related health requirements, slightly higher for children’s and teaching pools, and 38–40 °C for spa pools. A lower water temperature means a lower condensing temperature and a smaller pressure ratio, so the same compressor produces more heat and the COP is naturally higher.
4. The heat balance behind the holding load
In holding mode the heat pump is not replacing the heat needed to warm the pool; it is replacing the heat the pool loses. That loss has to be broken into items rather than guessed as watts per square meter.
| Loss item | Driven by | Engineering handling |
|---|---|---|
| Surface evaporation | Water temperature, humidity, air speed, cover | Night cover, limiting air speed in the hall, interlocking with the dehumidifier |
| Convection | Outdoor wind speed, exposure | Sheltered position, wind breaks |
| Radiation | Water temperature against surroundings | For indoor pools, envelope and air distribution |
| Shell conduction | Insulation detail, groundwater level | External insulation, breaking cold bridges |
| Make-up water heating | Make-up volume and temperature | Pre-heat make-up, limit make-up rate |
| Pipework losses | Insulation quality, plant-room temperature | Insulate, shorten runs |
Evaporation is usually over half the total, and a night cover cuts it and convection by 50–70%.
5. First heat-up and holding load are two separate sums
The first heat-up is plain thermodynamics: volume, temperature difference, time. Take a 500 m³ pool, make-up at 15 °C, target 27 °C, so ΔT = 12 K. The heat required is 500 × 1000 × 4.186 × 12 / 3600 ≈ 6 977 kWh. Spread over 48 hours that averages about 145 kW of net capacity, and the installed capacity has to sit above that once losses and efficiency are allowed for. For units of 25–40 kW, that means several in parallel.
The holding load is an order of magnitude smaller. A steady-state indoor pool typically loses 100–200 W per m² of water surface — higher outdoors, without a cover, or in wind — so a 500 m² pool may only need 50–100 kW. That is why many projects look undersized at start-up and adequate in service. A proposal that does not state which duty point it is sized on will be argued about later.
6. Reading COP and seasonal efficiency
COP is heat output divided by electrical input, and it only means anything with the test conditions attached. Commercial heat pump water heaters in China are tested to GB/T 21362-2023, which defines nominal COP and the annual heating seasonal performance factor (AHPF), with efficiency grades referring to GB 29541-2013. Pool heat pumps have no dedicated national efficiency method yet, so manufacturers test to the water-heater standard or to their own enterprise standard, and the conditions do not line up.
| What you are reading | What must be confirmed | Risk |
|---|---|---|
| Nominal COP | Test standard, dry/wet bulb, entering and leaving water, flow | Conditions not aligned, numbers not comparable |
| AHPF / seasonal efficiency | Calculation boundary, climate zone, load model | Southern weather data applied to a northern project |
| Part-load capability | Minimum frequency, modulation range, staging logic | Short cycling at low load, real consumption rises |
| Low-temperature capacity | Capacity and COP at the design outdoor temperature | Only mild-condition data, winter shortfall |
Before comparing two units, align five numbers: dry-bulb, wet-bulb, entering water, leaving water and flow.
7. Defrost is a survival requirement, not a feature
When outdoor air is cold and humid, the fin surface drops below 0 °C and moisture in the air deposits as frost. Frost blocks the air path, airflow falls, heat uptake falls, capacity falls, and the unit frosts faster — a self-reinforcing loop. There are four common strategies: reverse-cycle defrost with a four-way valve, hot-gas bypass, circuit-group rotation, and demand defrost driven by air pressure drop or a frost sensor. Reverse cycle is simple and thorough but pulls heat from the pool water, so the water temperature dips; group rotation and hot-gas bypass disturb the water less but cost more in controls and piping.
8. Five misconceptions worth correcting early
- “It cannot run below zero.” It can, with a cold-climate model and reliable defrost — but capacity must come from the local design temperature, not a mild-condition nameplate.
- “Higher COP always means a lower bill.” A unit rated 5.5 may give 2.8 at 0 °C; one rated 4.5 may still hold 3.5. Annual cost follows the seasonal curve.
- “Bigger is safer.” Oversizing causes short cycling at part load, which raises consumption and shortens compressor life.
- “Titanium means the exchanger is fine.” Wall thickness, velocity, pressure drop and cleanability decide whether it lasts.
- “Water treatment is a pool issue.” Scale and biofilm are a direct efficiency tax on the exchanger.
The six answers worth getting in writing before purchase, and how to read each one, are set out in technical data.
9. Air, water and ground are three different products
Pool heat pumps are classed by heat source; the cycle is identical, but capital cost, winter performance and site constraints differ.
| Heat source | Capital cost | Winter efficiency | Where it fits | Main constraint |
|---|---|---|---|---|
| Air | Low | Falls with air temperature | Most pools | Defrost, air-side clearance |
| Water | Medium | Relatively stable | Near surface water or usable reclaimed water | Abstraction and return, water treatment |
| Ground | High | Stable | Sites with land for boreholes, year-round load | Borehole area, ground thermal balance |
10. Where Longkang’s scope sits
Longkang supplies air-source heat pump water heaters and water chillers to hotels, schools, hospitals, factories and municipal environmental projects, and pool heating is one of the main applications of the air-source line. On a pool project the scope covers the heat load calculation from pool volume, surface, local weather, make-up method and operating hours; unit count and parallel arrangement for both holding load and first heat-up time; a selection sheet with exchanger material, pressure drop, connections and electrical data; drawing coordination with the design institute; and installation guidance, commissioning and spares.
Retrofits need one extra step: check the existing pump head and flow, plant-room space, air clearance, electrical capacity and whether the pipework needs a bypass. Skip those checks and even a correctly sized unit will not reach its design point.
The pool unit range itself sits under pool heat pump products; this section of the site is the engineering reference behind those selections.
The series at a glance
Principle and sizing — Heating process · Sizing · Technical data · Efficiency and COP
Product classes — Components · Performance classes · Form factors · Market outlook
Site and water — Water temperature · Corrosion · Installation · Indoor air · Applications
Answers — Pool heat pump FAQ · Sizing FAQ · Installation FAQ · Efficiency FAQ · Low temperature FAQ · Materials FAQ · Retrofit FAQ · Water quality FAQ · Indoor air FAQ · Acceptance FAQ · Maintenance FAQ
Related reading
Air-source heat pump water heaters: a full guide · Heat-pump COP ratings · Defrost logic and winter operation · Air-source heat pump sizing · Air-source heat pump product range