County Coal-to-Electric: Size for −12 °C, Not 7 °C

A county coal-to-electric program usually buys equipment quickly and then discovers that the problems are in three places the equipment cannot fix: a heat pump selected at a nominal 7 °C, a house still heated by 75 °C cast-iron radiators, and a village transformer that cannot carry the starting current. The compressor is rarely the cause.

The case below is a typical northern county household, not a single instrumented site. The numbers are order-of-magnitude values used to show the method; the installed capacity and the operating records of a specific project should come from its file.

1. Start with the coal baseline

A northern county household of 100–120 m² with a 120–150-day heating season commonly burns 2–3 t of coal a year. At 900 CNY/t, 2.5 t costs 2,250 CNY. That figure is both the benchmark for the post-retrofit electricity bill and a way to back-calculate the actual heat load.

At 6,000 kcal/kg and 70% stove efficiency, 2.5 t of coal delivers about 12,250 kWh of useful heat. Over 2,880 hours, the average load is about 4.3 kW. This is closer to the truth than an area index, because it is what the household actually burned.

2. Select on the low-temperature capacity, not the nameplate

The 12 kW on the brochure is a nominal rating at 7 °C or 20 °C. At −12 °C it delivers a little more than half. The correction below is typical for a standard cold-climate model; a low-temperature model holds a higher fraction, and the exact curve belongs to the selected model.

Outdoor temperature Capacity vs nominal Output of a 12 kW unit
7 °C 100% 12.0 kW
0 °C 82% 9.8 kW
−7 °C 68% 8.2 kW
−12 °C 58% 7.0 kW
−20 °C 45% 5.4 kW

A northern county design temperature is often −12 to −15 °C. At −12 °C, a 12 kW unit delivers 7.0 kW. A 100 m² house at 70 W/m² needs 7.0 kW. It is exactly enough, with no margin. A 130 m² house, a poorly insulated house or a high ceiling will not be covered.

Calculate the other way: 130 m² × 75 W/m² = 9.75 kW; divide by 0.58 to get the nameplate requirement, 16.8 kW; select 18 kW, not 12 kW. The first cold snap then shows full-speed operation, a supply temperature that will not rise, a room at 14–16 °C, an electric backup that doubles the bill, and the conclusion that “heat pumps do not work”. The real cause is the selection.

3. Grid capacity and emitters are the two front-end works

Grid. A single house needs 7–10 kW for heating plus domestic load, so the service capacity is 15–20 kW. A 100-house village needs 800–1,200 kW, and the existing transformer and low-voltage lines usually need upgrading. This work is the real bottleneck: it is large, slow and involves the utility.

Many “the heat pump is not heating” complaints end at a terminal voltage of 190 V. The compressor starts, protects and restarts dozens of times a day. A voltage stabilizer may mask the symptom; the fix is a larger service or a thicker line.

Emitters. A heat pump is designed for 45 °C water. A cast-iron radiator selected for 75 °C delivers only about 60% of its rated output at 45 °C. Without changing the emitter, the room will not reach temperature, whatever the heat pump size. Two options: increase the radiator area by 60–80%, or change to fan coils or underfloor heating. Emitter work is usually 20–30% of the project cost and cannot be left out of the budget.

4. Run the operating cost honestly

For a 100 m² house, 120 days and an average load of 4.3 kW, the annual heat is 4.3 × 2,880 = 12,384 kWh. At a seasonal COP of 2.2, including low-temperature operation, defrost and part load, the annual electricity is 12,384 ÷ 2.2 = 5,629 kWh.

Case Annual cost Indoor temperature Labor
Coal, 2.5 t at 900 CNY/t 2,250 CNY 14–18 °C Stoking, ash, night refill
Heat pump, flat tariff 0.50 CNY/kWh 2,815 CNY 18–20 °C None
Heat pump, off-peak 0.38 CNY/kWh 2,139 CNY 18–20 °C None

The honest conclusion is that at a flat tariff the heat pump costs more than coal, and at an off-peak tariff it costs less. The case for the program is comfort, labor, indoor air and local emissions, not always a lower bill. A proposal that promises a lower bill at a flat tariff is not credible.

5. What the county program should check

House-by-house heat load. Use the coal baseline where available, and an area index only as a cross-check. A 130 m² house with poor insulation is not the same load as a 100 m² house with a new envelope.

Low-temperature model. A standard unit may stop at −5 to −7 °C; a cold-climate unit may be rated to −15 or −25 °C. Match the model to the design temperature, not to the price.

Emitter survey. Count the radiator area, measure the existing supply temperature and decide whether to add area, change terminals or accept a lower room temperature. Do this before the heat pump is ordered.

Grid survey. Check the transformer, the service cable and the terminal voltage at the end of the line. A 190 V terminal is a red flag. Plan the upgrade with the utility before the heating season.

Defrost water. In a cold county, the defrost water must drain away from the unit and the walkway. A frozen drain pan or a sheet of ice under the unit is a common winter complaint.

Five failure points in coal-to-electric retrofits

Most coal-to-electric failures are not equipment faults. They are scope omissions that appear in the first winter and are then blamed on the heat pump. The five below account for most call-backs.

Failure Mechanism Prevention
Sizing on the nameplate A 12 kW nominal unit delivers about 7 kW at −12 °C Select on the low-temperature capacity table
Defrost water with no drainage Ice builds under the unit and on the walkway Drain pan, slope and freeze protection
Unit tight to the wall Inlet clearance under 300 mm cuts airflow and capacity Keep the inlet and outlet clear; check the plume path
No operator training Filters clog, defrost is misunderstood, freeze protection is switched off Leave a laminated card and a named contact
No O&M budget After three years, filters, refrigerant and pumps are neglected Include 3–5 years of service in the project budget

A county program can install thousands of units and still fail at the household level if these five are left to the installer’s discretion. Put them in the commissioning checklist and in the payment schedule, not in a brochure. The householder should be able to show where the defrost water goes and who to call when the unit stops.

The low-temperature capacity point is the one that decides comfort. A unit that keeps the room warm at −12 °C may need a much larger nominal rating than the heated area suggests; a unit selected on the 7 °C rating will run continuously and still fail. Longcom’s air-source heat pump page gives the cold-climate capacity tables used in this county example.

Common questions

Is a 12 kW unit enough for a 100 m² house?

At −12 °C it delivers about 7.0 kW, which exactly matches a 70 W/m² load. There is no margin for a cold snap, poor insulation or a higher ceiling.

Why does the unit run at full speed and still not heat?

Because it was selected on a 7 °C nominal capacity, or because the emitter cannot release 45 °C heat. Check both before adding electric backup.

Do radiators have to be replaced?

Not always. Adding 60–80% more radiator area can work. The decision depends on the existing area, the room and the available space.

Can a voltage stabilizer fix a weak grid?

It can mask the symptom, but the compressor still draws a high current at low voltage. The durable fix is a larger service or a thicker cable.

Is a heat pump cheaper than coal?

At a flat 0.50 CNY/kWh, this example costs 2,815 CNY against 2,250 CNY for coal. At an off-peak 0.38 CNY/kWh, it costs 2,139 CNY. The tariff, not the COP alone, decides.

What is the first survey item?

The coal baseline and the design outdoor temperature. Without them, the heat load and the low-temperature correction cannot be fixed.

Why size at -12 °C?

The cold snap sets the peak, not the average. A unit sized at 7 °C cannot meet the design day. Use the local extreme and the building load.

What baseline?

A measured coal or electric baseline for at least one season. Without it, the saving cannot be verified. Start with bills and a load survey.