Heat pumps · Chillers · Sludge drying systems
Frequently asked questions

Air-source heat pump questions

Air-source heat pump FAQ index: sizing, power use, defrost, noise, alarms, maintenance and lifecycle cost, linked to full LONGCOM technical guides.

Explore Air-source heat pump series products →

Quick engineering answers

Start with these eight answers

Does a COP of 4 mean four units of heat per unit of electricity?

It means four units of useful heat at the condenser for one unit of electrical input, but three of those units are moved from the air. The nominal COP is a test-point value, not a year-round average.

Read the full technical article →
Can a heat pump work at -15 °C?

A standard scroll unit loses much of its output; an EVI unit can hold heating at -15 °C. Size on the coldest month and include defrost losses, not on the annual average.

Read the full technical article →
How big should the cylinder be?

About 0.8–1.0 times the daily demand. Take the upper end for concentrated showers and the lower end for distributed washbasins; check the peak hour, not only the daily total.

Read the full technical article →
How far can the hot-water line run without a return loop?

Beyond 15–20 m to the farthest outlet, fit a return loop. Control the pump on temperature; a 24-hour loop wastes heat and pump energy.

Read the full technical article →
What is the first sign that the heat exchanger needs cleaning?

The water-side temperature difference rises by 2 K above the commissioning value at the same flow. Clean and check the water treatment before the COP falls further.

Read the full technical article →
How long does a heat-pump water heater last?

The unit is typically designed for 10–15 years and the cylinder for 8–12. Hard water, long running hours and skipped coil cleaning move the life toward the lower end.

Read the full technical article →
What is the first question to ask when sizing a heat pump?

How much hot water is drawn at the peak hour, not the daily total. The peak hour sizes the plant; the daily total only sets the tank. Get the fixture count and the draw profile.

Read the full technical article →
Which compressor is best for 60 °C water?

A standard scroll can reach 60 °C but may run close to its 65 °C condensing limit. A vapor-injection scroll or a high-temperature model is safer for 60–65 °C, especially in cold weather.

Read the full technical article →

Air-source heat pump water heaters are selected on daily demand, ambient temperature and peak draw, then commissioned on flow, defrost and control settings. This index groups the English guides by the decision you need to make, from first sizing to fault finding and lifecycle cost.

Each link opens a full article with assumptions, formulas and site checks. For a project-specific answer, send the duty conditions through the contact page.

Sizing, demand and operating cost

Installation, noise and defrost

Troubleshooting and water quality

Maintenance, lifespan and applications